PMAC2A-PC104 Hardware Manual
Base Board E-Point Jumper Descriptions
44
E18 – E19: PC/104 Bus Address
E Point and Physical
Layout
Location Description
Default
Jumpers E18 and E19 select the PC/104
bus address for communications
according to the following table:
E18 E19
Address
(Hex)
Address
(Dec)
OFF OFF $200 512
OFF ON $210 528
ON OFF $220 544
E18
E19
D4
ON ON $230 560
No E18 jumper
installed;
Jumper E19
installed
Note
Jumper E18 must be removed and jumper E19 must be installed for using either
the Ethernet or USB optional methods of communication.